AS ALWAYS, PLEASE CHECK WITH YOUR LOCAL
         HOUSING AUTHORITY FOR  SPECIFIC COMPLIANCE INFORMATION
        
[Code 
        of Federal Regulations]
        [Title 24, Volume 4]
        [Revised as of April 1, 2002]
        From the U.S. Government Printing Office via GPO Access
        [CITE: 24CFR982.401]
[Page 
        580-583]
        TITLE 24--HOUSING AND URBAN DEVELOPMENT
        CHAPTER IX--OFFICE OF ASSISTANT SECRETARY FOR PUBLIC AND INDIAN HOUSING, 
        
        DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT
PART 
        982--SECTION 8 TENANT BASED ASSISTANCE: 
        HOUSING CHOICE VOUCHER PROGRAM--Table of Contents
         
        
        Subpart I--Dwelling Unit: Housing Quality Standards, Subsidy Standards, 
        
        Inspection and Maintenance
        
        Sec. 982.401 Housing quality standards (HQS).
Source: 60 FR 34695, July 3, 1995, unless otherwise noted.
(a) 
        Performance and acceptability requirements. (1) This section states 
        the housing quality standards (HQS) for housing assisted in the programs.
        (2)(i) The HQS consist of:
        (A) Performance requirements; and
        (B) Acceptability criteria or HUD approved variations in the acceptability 
        criteria.
        (ii) This section states performance and acceptability criteria 
        for these key aspects of housing quality:
        (A) Sanitary facilities;
        (B) Food preparation and refuse disposal;
        (C) Space and security;
        (D) Thermal environment;
        (E) Illumination and electricity;
        (F) Structure and materials;
        (G) Interior air quality;
        (H) Water supply;
        (I) Lead-based paint;
        (J) Access;
        (K) Site and neighborhood;
        (L) Sanitary condition; and
        (M) Smoke detectors.
        (3) All program housing must meet the HQS performance requirements 
        both at commencement of assisted occupancy, and throughout the assisted 
        tenancy.
        (4)(i) In addition to meeting HQS performance requirements, the 
        housing must meet the acceptability criteria stated in this section, unless 
        variations are approved by HUD.
        (ii) HUD may approve acceptability criteria variations for the 
        following purposes:
        (A) Variations which apply standards in local housing codes or 
        other codes adopted by the PHA; or
 (B) 
        Variations because of local climatic or geographic conditions.
        (iii) Acceptability criteria variations may only be approved by 
        HUD 
        pursuant to paragraph (a)(4)(ii) of this section if such variations either:
        (A) Meet or exceed the performance requirements; or
        (B) Significantly expand affordable housing opportunities for families 
        assisted under the program.
        (iv) HUD will not approve any acceptability criteria variation 
        if HUD believes that such variation is likely to adversely affect the 
        health or safety of participant families, or severely restrict housing 
        choice.
        (b) Sanitary facilities--(1) Performance requirements. The 
        dwelling unit must include sanitary facilities located in the unit. The 
        sanitary facilities must be in proper operating condition, and adequate 
        for personal cleanliness and the disposal of human waste. The sanitary 
        facilities must be usable in privacy.
        (2) Acceptability criteria. (i) The bathroom must be located 
        in a separate private room and have a flush toilet in proper operating 
        condition.
        (ii) The dwelling unit must have a fixed basin in proper operating 
        condition, with a sink trap and hot and cold running water.
        (iii) The dwelling unit must have a shower or a tub in proper operating 
        condition with hot and cold running water.
        (iv) The facilities must utilize an approvable public or private 
        disposal system (including a locally approvable septic system).
        (c) Food preparation and refuse disposal--(1) Performance 
        requirement. (i) The dwelling unit must have suitable space and 
        equipment to store, prepare, and serve foods in a sanitary manner.
        (ii) There must be adequate facilities and services for the sanitary 
        disposal of food wastes and refuse, including facilities for temporary 
        storage where necessary (e.g, garbage cans).
        (2) Acceptability criteria. (i) The dwelling unit must have 
        an oven, and a stove or range, and a refrigerator of appropriate size 
        for the family. All of the equipment must be in proper operating condition. 
        The equipment may be supplied by either the owner or the family. A microwave 
        oven may be substituted for a tenant-supplied oven and stove or range. 
        A microwave oven may be substituted for an owner-supplied oven and stove 
        or range if the tenant agrees and microwave ovens are furnished instead 
        of an oven and stove or range to both subsidized and unsubsidized tenants 
        in the building or premises.
        (ii) The dwelling unit must have a kitchen sink in proper operating 
        condition, with a sink trap and hot and cold running water. The sink must 
        drain into an approvable public or private system.
        (iii) The dwelling unit must have space for the storage, preparation, 
        and serving of food.
        (iv) There must be facilities and services for the sanitary disposal 
        of food waste and refuse, including temporary storage facilities where 
        necessary (e.g., garbage cans).
        (d) Space and security--(1) Performance requirement. The 
        dwelling unit must provide adequate space and security for the family.
        (2) Acceptability criteria. (i) At a minimum, the dwelling 
        unit must have a living room, a kitchen area, and a bathroom.
        (ii) The dwelling unit must have at least one bedroom or living/sleeping 
        room for each two persons. Children of opposite sex, other than very young 
        children, may not be required to occupy the same bedroom or living/sleeping 
        room.
        (iii) Dwelling unit windows that are accessible from the outside, 
        such as basement, first floor, and fire escape windows, must be lockable 
        (such as window units with sash pins or sash locks, and combination windows 
        with latches). Windows that are nailed shut are acceptable only if these 
        windows are not needed for ventilation or as an alternate exit in case 
        of fire.
        (iv) The exterior doors of the dwelling unit must be lockable. 
        Exterior doors are doors by which someone can enter or exit the dwelling 
        unit.
        (e) Thermal environment--(1) Performance requirement. The 
        dwelling unit must have and be capable of maintaining a thermal environment 
        healthy for the human body.
        (2) Acceptability criteria. (i) There must be a safe system for 
        heating the dwelling unit (and a safe cooling system, where present). 
        The system must be in proper operating condition. The system must be able 
        to provide adequate heat (and cooling, if applicable), either directly 
        or indirectly, to each room, in order to assure a healthy living environment 
        appropriate to the climate.
        (ii) The dwelling unit must not contain unvented room heaters that 
        burn gas, oil, or kerosene. Electric heaters are acceptable.
        (f) Illumination and electricity--(1) Performance requirement. 
        Each room must have adequate natural or artificial illumination to permit 
        normal indoor activities and to support the health and safety of occupants. 
        The dwelling unit must have sufficient electrical sources so occupants 
        can use essential electrical appliances. The electrical fixtures and wiring 
        must ensure safety from fire.
        (2) Acceptability criteria. (i) There must be at least one 
        window in the living room and in each sleeping room.
        (ii) The kitchen area and the bathroom must have a permanent ceiling 
        or wall light fixture in proper operating condition. The kitchen area 
        must also have at least one electrical outlet in proper operating condition.
        (iii) The living room and each bedroom must have at least two electrical 
        outlets in proper operating condition. Permanent overhead or wall-mounted 
        light fixtures may count as one of the required electrical outlets.
        (g) Structure and materials--(1) Performance requirement. 
        The dwelling unit must be structurally sound. The structure must not present 
        any threat to the health and safety of the occupants and must protect 
        the occupants from the environment.
        (2) Acceptability criteria. (i) Ceilings, walls, and floors 
        must not have any serious defects such as severe bulging or leaning, large 
        holes, loose surface materials, severe buckling, missing parts, or other 
        serious damage.
        (ii) The roof must be structurally sound and weathertight.
        (iii) The exterior wall structure and surface must not have any 
        serious defects such as serious leaning, buckling, sagging, large holes, 
        or defects that may result in air infiltration or vermin infestation.
        (iv) The condition and equipment of interior and exterior stairs, 
        halls, porches, walkways, etc., must not present a danger of tripping 
        and falling. For example, broken or missing steps or loose boards are 
        unacceptable.
        (v) Elevators must be working and safe.
        (h) Interior air quality--(1) Performance requirement. The 
        dwelling unit must be free of pollutants in the air at levels that threaten 
        the health of the occupants.
        (2) Acceptability criteria. (i) The dwelling unit must be 
        free from dangerous levels of air pollution from carbon monoxide, sewer 
        gas, fuel gas, dust, and other harmful pollutants.
        (ii) There must be adequate air circulation in the dwelling unit.
        (iii) Bathroom areas must have one openable window or other adequate 
        exhaust ventilation.
        (iv) Any room used for sleeping must have at least one window. 
        If the window is designed to be openable, the window must work.
        (i) Water supply--(1) Performance requirement. The water 
        supply must be free from contamination.
        (2) Acceptability criteria. The dwelling unit must be served by 
        an approvable public or private water supply that is sanitary and free 
        from contamination.
        (j) Lead-based paint performance requirement. The Lead-Based Paint 
        Poisoning Prevention Act (42 U.S.C. 4821-4846), the Residential Lead-Based 
        Paint Hazard Reduction Act of 1992 (42 U.S.C. 4851-4856), and implementing 
        regulations at part 35, subparts A, B, M, and R of this title apply to 
        units assisted under this part.
        (k) Access performance requirement. The dwelling unit must be able 
        to be used and maintained without unauthorized use of other private properties. 
        The building must provide an alternate means of exit in case of fire (such 
        as fire stairs or egress through windows).
        (l) Site and Neighborhood--(1) Performance requirement. 
        The site and neighborhood must be reasonably free from disturbing noises 
        and reverberations and other dangers to the health, safety, and general 
        welfare of the occupants.
        (2) Acceptability criteria. The site and neighborhood may not be 
        subject to serious adverse environmental conditions, natural or manmade, 
        such as dangerous walks or steps; instability; flooding, poor drainage, 
        septic tank back-ups or sewage hazards; mudslides; abnormal air pollution, 
        smoke or dust; excessive noise, vibration or vehicular traffic; excessive 
        accumulations of trash; vermin or rodent infestation; or fire hazards.
        (m) Sanitary condition--(1) Performance requirement. The 
        dwelling unit and its equipment must be in sanitary condition.
        (2) Acceptability criteria. The dwelling unit and its equipment 
        must be free of vermin and rodent infestation.
        (n) Smoke detectors performance requirement--(1) Except 
        as provided in paragraph (n)(2) of this section, each dwelling unit must 
        have at least one battery-operated or hard-wired smoke detector, in proper 
        operating condition, on each level of the dwelling unit, including basements 
        but excepting crawl spaces and unfinished attics. Smoke detectors must 
        be installed in accordance with and meet the requirements of the National 
        Fire Protection Association Standard (NFPA) 74 (or its successor standards). 
        If the dwelling unit is occupied by any hearing-impaired person, - smoke 
        detectors must have an alarm system, designed for hearing-impaired persons 
        as specified in NFPA 74 (or successor standards).
        (2) For units assisted prior to April 24, 1993, owners who installed 
        battery-operated or hard-wired smoke detectors prior to April 24, 1993 
        in compliance with HUD's smoke detector requirements, including the regulations 
        published on July 30, 1992, (57 FR 33846), will not be required subsequently 
        to comply with any additional requirements mandated by NFPA 74 (i.e., 
        the owner would not be required to install a smoke detector in a basement 
        not used for living purposes, nor would the owner be required to change 
        the location of the smoke detectors that have already been installed on 
        the other floors of the unit).
[60 
        FR 34695, July 3, 1995, as amended at 61 FR 27163, May 30, 1996; 63 
        FR 23861, Apr. 30, 1998; 64 FR 26646, May 14, 1999; 64 FR 49658, Sept. 
        
        14, 1999; 64 FR 50230, Sept. 15, 1999]
          

 Relay Service